Outages
Below you will find a list of power outages with date, location,
duration, and cause. Outages included in this section were in
excess of 30 minutes and/or are a planned outage situation.
March 2, 2009
Location: Hatteras Island
Duration: 10:07 PM – 3:30 AM – 5 hour 27 minutes
Cause: Shackle broke on transmission line
September 8, 2008
Location: Hatteras Island and Ocracoke
Duration: 7:06 – 8:03 – 1 hour 29 minutes
Cause: Shackle holding a transmission line insulator failed
June 13, 2008
Location: Waves and Rodanthe
Duration: 6:01 – 7:05 – 1 hour 4 minutes
Cause: Equipment malfunction in the Waves substation.
Location: Salvo and Waves
Duration: 6:01 – 8:34 – 2 hours 33 minutes
Cause: Equipment malfunction in the Waves substation.
November 2, 2007
Location: Hatteras and Ocracoke Islands
Duration: 16:42 – 19:27 – 2 hours 45 minutes
Cause: Hardware failure on 115kV transmission line at Oregon Inlet during high wind event from Hurricane Noel.
September 13, 2007
Location: Buxton, Frisco, Hatteras, and Tideland’s consumers on Ocracoke
Duration: 05:07 - 05:58 - 51 minutes
Cause: Salt contamination on the insulators in the Buxton 115kV substation causing a flashover.
August 10, 2007
Location: Rodanthe, Waves and Salvo
Duration: 06:08 - 07:49 - 1 hour 41 minutes
Cause: Lightning strike caused circuit switcher in Waves substation to open.
July 24, 2007
Location: Frisco and Hatteras
Duration: 03:45 - 04:59- 1 hour 14 minutes
Cause: Blown lightning arrestor on the service transformer that serves the Tideland substation in Hatteras.
May 22, 2007
Location: Hatteras
Duration: 22:17 to 23:12 - 55 minutes
Cause: Cat on substation breaker tripped Hatteras substation off.
May 7, 2007
Location: Frisco, Hatteras, Ocracoke
Duration: 17:26 to 18:11 - 45 minutes
Cause: Salt contamination on insulators in Frisco substation caused 34.5 kV line to trip off.
April 4, 2007
Location: Buxton
Duration: 06:10 to 07:15 - 1 hour 5 minutes
Cause: Lightning during heavy thunderstorm caused circuit switcher at Buxton Generation Plant to open.
November 23, 2006
Location: Hatteras and Ocracoke Islands
Duration: 13:39 to 14:35 – 56 minutes
Cause: NCDOT crews clearing sand from Highway 12 just north of Rodanthe struck and broke a guy wire which flew up and over the transmission line
November 22, 2006
Location: Buxton
Duration: 21:42 to 22:10 – 28 minutes
Cause: Arcing on 115kV transmission line switch in Avon
November 22, 2006
Location: Buxton
Duration: 05:15 to 21:37 – 16 hours, 22 minutes
Cause: Broken pole on Dominion Power 115kV transmission line just south of Colington
November 22, 2006
Location: Frisco
Duration: 05:15 to 22:15 – 17 hours, 0 minutes
Cause: Broken pole on Dominion Power 115kV transmission line just south of Colington
November 22, 2006
Location: Hatteras
Duration: 05:15 to 22:20 – 17 hours, 5 minutes
Cause: Broken pole on Dominion Power 115kV transmission line just south of Colington
November 22, 2006
Location: Avon
Duration: 05:15 to 21:35 – 16 hours, 20 minutes
Cause: Broken pole on Dominion Power 115kV transmission line just south of Colington
November 22, 2006
Location: Waves
Duration: 05:15 to 21:34 – 16 hours, 19 minutes
Cause: Broken pole on Dominion Power 115kV transmission line just south of Colington
November 21, 2006
Location: Waves and Avon
Duration: 18:14 to 19:56 – 1 hour, 42 minutes
Cause: Insulator failure on 115kV transmission line south of Avon
November 21, 2006
Location: Buxton, Frisco, Hatteras and Ocracoke
Duration: 18:14 to 20:39 – 2 hours, 25 minutes
Cause: Insulator failure on 115kV transmission line south of Avon
September 1, 2006
Location: Frisco
Duration: 22:00 to 23:35 - 1 hour, 35 minutes
Cause: Snake on transformer in Frisco Substation
May 1, 2006
Location: Hatteras Island and Ocracoke
Duration: 7:14 to 08:01 - 47 minutes
Cause: Buxton generating plant tripped off after unexpected load increase. Delay in restoration caused by mechanical problems with transmission line switch
September 15, 2005
Location: Hatteras Substation Village Circuit
Duration: 20:24 to 20:54 - 30 minutes
Cause: Circuit opened for line repairs during storm restoration (Hurricane Ophelia)
September 15, 2005
Location: Buxton Substation South Circuit
Duration: 08:54 to 14:11 - 5 hours, 17 minutes
Cause: High winds during Hurricane Ophelia (34.5 KV line problem)
September 15, 2005
Location: Buxton Substation North Circuit
Duration: 08:54 to 14:38 - 5 hours, 44 minutes
Cause: High winds during Hurricane Ophelia (34.5 KV line problem)
September 15, 2005
Location: Frisco Substation North Circuit
Duration: 08:54 to 15:32 - 6 hours, 38 minutes
Cause: High winds during Hurricane Ophelia (34.5 KV line problem)
September 15, 2005
Location: Frisco Substation South Circuit
Duration: 08:54 to 16:44 - 7 hours, 50 minutes
Cause: High winds during Hurricane Ophelia (34.5 KV line problem)
September 15, 2005
Location: Hatteras Substation Village Circuit
Duration: 08:06 to 17:14 - 9 hours, 8 minutes
Cause: High winds during Hurricane Ophelia
September 15, 2005
Location: Hatteras Substation Beach Circuit
Duration: 08:54 to 17:16 - 8 hours, 22 minutes
Cause: High winds during Hurricane Ophelia (34.5 KV line problem)
September 15, 2005
Location: Hatteras Substation Dock Circuit
Duration: 08:54 to 17:54 - 9 hours,0 minutes
Cause: High winds during Hurricane Ophelia (34.5 KV line problem)
August 25 , 2005
Location: Hatteras and Ocracoke Islands
Duration: 11:40 to 11:47 - 7 minutes
Cause: Planned outage to remove toy kite and string from transmnission line
August 1, 2005
Location: Buxton South Circuit
Duration: 08:13 to 09:19 - 1 hour 6 minutes
Cause: Insulator failure
August 1, 2005
Location: Buxton North Circuit, Frisco, and Hatteras
Duration: 08:13 to 08:55 - 42 minutes
Cause: Insulator failure created flashover to transmission line
July 17, 2005
Location: Waves North Circuit - Rodanthe, Northern Waves
Duration: 09:00 to 10:52 - 1 hour 52 minutes
Cause: Relay malfunction in Waves Substation
July 17, 2005
Location: Waves South Circuit - Salvo, Southern Waves
Duration: 09:00 to 10:18 - 1 hour 18 minutes
Cause: Relay malfunction in Waves Substation
July 13, 2005
Location: Frisco, Hatteras and Ocracoke
Duration: 05:37 to 07:31 - 1 hour 54 minutes
Cause: Lightning struck 34.5kV recloser at Buxton substation
July 13, 2005
Location: Buxton
Duration: 05:37 to 06:53 - 1 hour 16 minutes
Cause: Lightning struck 34.5kV recloser at Buxton substation
June 2, 2005
Location: Entire Island including Ocracoke
Duration: 12:17 to 15:45 - 3 hours 28 minutes
Cause: Insulator failed on 115kV line at Oregon Inlet
May 6, 2005
Location: Waves Substation - South Circuit
Duration: 13:43 to 16:03 - 2 hours 20 minutes
Cause: High winds from storm broke jumpers on main line
May 6, 2005
Location: Waves Substation - North Circuit
Duration: 13:43 to 14:29 - 46 minutes
Cause: Circuit switcher in Waves Substation tripped when South Circuit recloser opened
April 21, 2005
Location: Avon Substation - all circuits
Duration: 23:33 to 00:57 - 1 hour 24 minutes
Cause: Salt contamination on substation insulators caused flashover
March 8, 2005
Location: Avon Substation - all circuits
Duration: 20:39 to 21:52 - 1 hour 13 minutes
Cause: Jumper broke on station transformer during high wind event.
March 8, 2005
Location: Buxton South Circuit
Duration: 13:12 to 13:37 - 25 minutes
Cause: High winds blew debris into line
December 16 , 2004
Location: Waves Substation
Duration: 13:42 to 14:26 - 44 minutes
Cause: Insulator failed on 115 KV line
December 16 , 2004
Location: Ocracoke Substation
Duration: 13:42 to 17:10 - 3 hours, 28 minutes
Cause: Insulator failed on 115 KV line
December 16 , 2004
Location: Buxton 34.5 KV Substation
Duration: 13:42 to 17:16 - 3 hours, 34 minutes
Cause: Insulator failed on 115 KV line
December 16 , 2004
Location: Frisco and Hatteras Substations
Duration: 13:42 to 17:13 - 3 hours, 31 minutes
Cause: Insulator failed on 115 KV line
December 16 , 2004
Location: Avon Substation
Duration: 13:42 to 16:14 - 2 hours, 32 minutes
Cause: Insulator failed on 115 KV line
August 15, 2004
Location: Avon Substation - Village Circuit
Duration: 16:04 to 16:41 - 37 minutes
Cause: Wire down in Avon Village
August 3, 2004
Location: Hatteras Beach, Dock, and Village Ckts
Duration: 11:42 to 19:57 - 8 hours 15 minutes
Cause: Hurricane Alex (some scattered outages remained after this time)
August 3, 2004
Location: Frisco North and South Circuits
Duration: 11:42 to 20:38 (North), 11:42 to 18:47 (South)
Cause: Hurricane Alex (some scattered outages remained after this time)
August 3, 2004
Location: Buxton North and South Circuits
Duration: 11:42 to 13:57 (North), 11:42 to 21:25 (South)
Cause: Hurricane Alex (some scattered outages remained after this time)
August 3, 2004
Location: Avon North and South Circuits
Duration: 11:42 to 13:23 - 1 hour 41 minutes
Cause: Hurricane Alex (some scattered outages remained after this time)
August 3, 2004
Location: Waves North and South Circuits
Duration: 11:42 to 13:23 - 1 hour 41 minutes
Cause: Hurricane Alex (some scattered outages remained after this time)
August 3, 2004
Location: Avon Village Circuit
Duration: 11:42 to 17:17 - 7 hours 35 minutes
Cause: Hurricane Alex (some scattered outages remained after this time)
July 21, 2004
Location: Buxton, Frisco, and Hatteras Substations, Ocracoke
Duration: 05:27 to 06:11 - 44 minutes
Cause: Lightning in Buxton 115/34.5kV Substation
June 11, 2004
Location: Frisco and Hatteras Substations, Ocracoke
Duration: 01:51 to 04:39 - 2 hr, 00 min (total, 5 interruption)
Cause: Lightning struck Buxton power Plant and Buxton transmission substation.
June 11, 2004
Location: Buxton 34.5 kV Substation
Duration: 01:51 to 04:36 - 1 hr, 36 min (total, 5 interruption)
Cause: Lightning struck Buxton power Plant and Buxton transmission substation.
May 22, 2004
Location: Buxton, Frisco & Hatteras Substations, Ocracoke
Duration: 21:08 to 21:46 - 38 min
Cause: Equipment malfunction. Voltage regulator control at Buxton caused 34.5 kV line to trip
May 4, 2004
Location: Avon Substation
Duration: 06:37 to 07:47 - 1 hr, 10 min
Cause: Buxton generating plant tripped line off during maintenance of transmission line.
March 17, 2004
Location: Waves Substation
Duration: 14:32 to 15:21 - 49 min
Cause: Switching problems during planned outage to maintain 115 kV switches at Oregon Inlet
March 17, 2004
Location: Avon Substation
Duration: 14:32 to 15:13 - 41 min
Cause: Switching problems during planned outage to maintain 115 kV switches at Oregon Inlet
March 13, 2004
Location: Avon Substation
Duration: 04:04 to 05:48 - 1 hr, 44 min
Cause: Perform maintenance on 115 kV switches
March 12, 2004
Location: Waves Substation
Duration: 04:02 to 05:47 - 1 hr, 45 min
Cause: Planned outage to repair 115 kV switch
March 8, 2004
Location: Waves Substation
Duration: 14:01 to15:20 - 1 hr, 19 min
Cause: Planned outage to repair 115 kV Switch at Waves Substation
|