Below you will find a list of power outages with date, location, duration, and cause. Outages included in this section were in excess of 30 minutes and/or are a planned outage situation.

June 6, 2010
Location:    Hatteras Island
Duration:    2:51 PM - 3:49 PM (58 min)
Cause   :    Wind Surfing Kite in Transmission Line @ New Inlet

April 30, 2010
Location:    Avon Village
Duration:    12:05 AM - 1:58 AM (1 hr. 53 min)
Cause   :    Repairs and Upgrades to Avon Substation,
                    Removal of Mobile Substation

April 26, 2010
Location:    Avon Village
Duration:    12:16AM - 2:27 AM (2 hr. 11 min.)
Cause   :    Placed Mobile Substation in Service

December 17, 2009
Location:  Frisco and Hatteras Villages
Duration: 12:01 AM - 1:37 AM (1 hr. 36 min.)
Cause:  Buxton Plant Black Start Test

November 11, 2009
Location:  Hatteras Island
Duration:  10:54PM - 4:50AM (5 hrs 56 min.)
Cause:  Dominion insulator failure

March 30, 2009
Location:  Frisco and Hatteras Village
Duration:  7:34 PM - 8:25 PM (51 min)
Cause:  Contractor cut Transfer/Trip Cable 34


March 2, 2009

Location: Hatteras Island
Duration: 10:07 PM 3:30 AM 5 hour 27 minutes
Cause: Shackle broke on transmission line

September 8, 2008
Location: Hatteras Island and Ocracoke
Duration: 7:06 8:03 1 hour 29 minutes
Cause: Shackle holding a transmission line insulator failed

June 13, 2008
Location: Waves and Rodanthe
Duration: 6:01 7:05 1 hour 4 minutes
Cause: Equipment malfunction in the Waves substation.

Location: Salvo and Waves
Duration: 6:01 8:34 2 hours 33 minutes
Cause: Equipment malfunction in the Waves substation.

November 2, 2007
Location: Hatteras and Ocracoke Islands
Duration: 16:42 19:27 2 hours 45 minutes
Cause: Hardware failure on 115kV transmission line at Oregon Inlet during high wind event from Hurricane Noel.

September 13, 2007
Location: Buxton, Frisco, Hatteras, and Tidelands consumers on Ocracoke
Duration: 05:07 - 05:58 - 51 minutes
Cause: Salt contamination on the insulators in the Buxton 115kV substation causing a flashover.

August 10, 2007
Location: Rodanthe, Waves and Salvo
Duration: 06:08 - 07:49 - 1 hour 41 minutes
Cause: Lightning strike caused circuit switcher in Waves substation to open.

July 24, 2007
Location: Frisco and Hatteras
Duration: 03:45 - 04:59- 1 hour 14 minutes
Cause: Blown lightning arrestor on the service transformer that serves the Tideland substation in Hatteras.

May 22, 2007
Location: Hatteras
Duration: 22:17 to 23:12 - 55 minutes
Cause: Cat on substation breaker tripped Hatteras substation off.

May 7, 2007
Location: Frisco, Hatteras, Ocracoke
Duration: 17:26 to 18:11 - 45 minutes
Cause: Salt contamination on insulators in Frisco substation caused 34.5 kV line to trip off.

April 4, 2007
Location: Buxton
Duration: 06:10 to 07:15 - 1 hour 5 minutes
Cause: Lightning during heavy thunderstorm caused circuit switcher at Buxton Generation Plant to open.

November 23, 2006
Location: Hatteras and Ocracoke Islands
Duration: 13:39 to 14:35 56 minutes
Cause: NCDOT crews clearing sand from Highway 12 just north of Rodanthe struck and broke a guy wire which flew up and over the transmission line

November 22, 2006
Location: Buxton
Duration: 21:42 to 22:10 28 minutes
Cause: Arcing on 115kV transmission line switch in Avon

November 22, 2006
Location: Buxton
Duration: 05:15 to 21:37 16 hours, 22 minutes
Cause: Broken pole on Dominion Power 115kV transmission line just south of Colington

November 22, 2006
Location: Frisco
Duration: 05:15 to 22:15 17 hours, 0 minutes
Cause: Broken pole on Dominion Power 115kV transmission line just south of Colington

November 22, 2006
Location: Hatteras
Duration: 05:15 to 22:20 17 hours, 5 minutes
Cause: Broken pole on Dominion Power 115kV transmission line just south of Colington

November 22, 2006
Location: Avon
Duration: 05:15 to 21:35 16 hours, 20 minutes
Cause: Broken pole on Dominion Power 115kV transmission line just south of Colington

November 22, 2006
Location: Waves
Duration: 05:15 to 21:34 16 hours, 19 minutes
Cause: Broken pole on Dominion Power 115kV transmission line just south of Colington

November 21, 2006
Location: Waves and Avon
Duration: 18:14 to 19:56 1 hour, 42 minutes
Cause: Insulator failure on 115kV transmission line south of Avon

November 21, 2006
Location: Buxton, Frisco, Hatteras and Ocracoke
Duration: 18:14 to 20:39 2 hours, 25 minutes
Cause: Insulator failure on 115kV transmission line south of Avon

September 1, 2006
Location: Frisco
Duration: 22:00 to 23:35 - 1 hour, 35 minutes
Cause: Snake on transformer in Frisco Substation

May 1, 2006
Location: Hatteras Island and Ocracoke
Duration: 7:14 to 08:01 - 47 minutes
Cause: Buxton generating plant tripped off after unexpected load increase. Delay in restoration caused by mechanical problems with transmission line switch

September 15, 2005
Location: Hatteras Substation Village Circuit
Duration: 20:24 to 20:54 - 30 minutes
Cause: Circuit opened for line repairs during storm restoration (Hurricane Ophelia)

September 15, 2005
Location: Buxton Substation South Circuit
Duration: 08:54 to 14:11 - 5 hours, 17 minutes
Cause: High winds during Hurricane Ophelia (34.5 KV line problem)

September 15, 2005
Location: Buxton Substation North Circuit
Duration: 08:54 to 14:38 - 5 hours, 44 minutes
Cause: High winds during Hurricane Ophelia (34.5 KV line problem)

September 15, 2005
Location: Frisco Substation North Circuit
Duration: 08:54 to 15:32 - 6 hours, 38 minutes
Cause: High winds during Hurricane Ophelia (34.5 KV line problem)

September 15, 2005
Location: Frisco Substation South Circuit
Duration: 08:54 to 16:44 - 7 hours, 50 minutes
Cause: High winds during Hurricane Ophelia (34.5 KV line problem)

September 15, 2005
Location: Hatteras Substation Village Circuit
Duration: 08:06 to 17:14 - 9 hours, 8 minutes
Cause: High winds during Hurricane Ophelia

September 15, 2005
Location: Hatteras Substation Beach Circuit
Duration: 08:54 to 17:16 - 8 hours, 22 minutes
Cause: High winds during Hurricane Ophelia (34.5 KV line problem)

September 15, 2005
Location: Hatteras Substation Dock Circuit
Duration: 08:54 to 17:54 - 9 hours,0 minutes
Cause: High winds during Hurricane Ophelia (34.5 KV line problem)

August 25 , 2005
Location: Hatteras and Ocracoke Islands
Duration: 11:40 to 11:47 - 7 minutes
Cause: Planned outage to remove toy kite and string from transmnission line

August 1, 2005
Location: Buxton South Circuit
Duration: 08:13 to 09:19 - 1 hour 6 minutes
Cause: Insulator failure

August 1, 2005
Location: Buxton North Circuit, Frisco, and Hatteras
Duration: 08:13 to 08:55 - 42 minutes
Cause: Insulator failure created flashover to transmission line

July 17, 2005
Location: Waves North Circuit - Rodanthe, Northern Waves
Duration: 09:00 to 10:52 - 1 hour 52 minutes
Cause: Relay malfunction in Waves Substation

July 17, 2005
Location: Waves South Circuit - Salvo, Southern Waves
Duration: 09:00 to 10:18 - 1 hour 18 minutes
Cause: Relay malfunction in Waves Substation

July 13, 2005
Location: Frisco, Hatteras and Ocracoke
Duration: 05:37 to 07:31 - 1 hour 54 minutes
Cause: Lightning struck 34.5kV recloser at Buxton substation

July 13, 2005
Location: Buxton
Duration: 05:37 to 06:53 - 1 hour 16 minutes
Cause: Lightning struck 34.5kV recloser at Buxton substation

June 2, 2005
Location: Entire Island including Ocracoke
Duration: 12:17 to 15:45 - 3 hours 28 minutes
Cause: Insulator failed on 115kV line at Oregon Inlet

May 6, 2005
Location: Waves Substation - South Circuit
Duration: 13:43 to 16:03 - 2 hours 20 minutes
Cause: High winds from storm broke jumpers on main line

May 6, 2005
Location: Waves Substation - North Circuit
Duration: 13:43 to 14:29 - 46 minutes
Cause: Circuit switcher in Waves Substation tripped when South Circuit recloser opened

April 21, 2005
Location: Avon Substation - all circuits
Duration: 23:33 to 00:57 - 1 hour 24 minutes
Cause: Salt contamination on substation insulators caused flashover

March 8, 2005
Location: Avon Substation - all circuits
Duration: 20:39 to 21:52 - 1 hour 13 minutes
Cause: Jumper broke on station transformer during high wind event.

March 8, 2005
Location: Buxton South Circuit
Duration: 13:12 to 13:37 - 25 minutes
Cause: High winds blew debris into line

December 16 , 2004 Location: Waves Substation
Duration: 13:42 to 14:26 - 44 minutes
Cause: Insulator failed on 115 KV line

December 16 , 2004
Location: Ocracoke Substation
Duration: 13:42 to 17:10 - 3 hours, 28 minutes
Cause: Insulator failed on 115 KV line

December 16 , 2004
Location: Buxton 34.5 KV Substation
Duration: 13:42 to 17:16 - 3 hours, 34 minutes
Cause: Insulator failed on 115 KV line

December 16 , 2004
Location: Frisco and Hatteras Substations
Duration: 13:42 to 17:13 - 3 hours, 31 minutes
Cause: Insulator failed on 115 KV line

December 16 , 2004
Location: Avon Substation
Duration: 13:42 to 16:14 - 2 hours, 32 minutes
Cause: Insulator failed on 115 KV line

August 15, 2004
Location: Avon Substation - Village Circuit
Duration: 16:04 to 16:41 - 37 minutes
Cause: Wire down in Avon Village

August 3, 2004
Location: Hatteras Beach, Dock, and Village Ckts
Duration: 11:42 to 19:57 - 8 hours 15 minutes
Cause: Hurricane Alex (some scattered outages remained after this time)

August 3, 2004
Location: Frisco North and South Circuits
Duration: 11:42 to 20:38 (North), 11:42 to 18:47 (South)
Cause: Hurricane Alex (some scattered outages remained after this time)

August 3, 2004
Location: Buxton North and South Circuits
Duration: 11:42 to 13:57 (North), 11:42 to 21:25 (South)
Cause: Hurricane Alex (some scattered outages remained after this time)

August 3, 2004
Location: Avon North and South Circuits
Duration: 11:42 to 13:23 - 1 hour 41 minutes
Cause: Hurricane Alex (some scattered outages remained after this time)

August 3, 2004
Location: Waves North and South Circuits
Duration: 11:42 to 13:23 - 1 hour 41 minutes
Cause: Hurricane Alex (some scattered outages remained after this time)

August 3, 2004
Location: Avon Village Circuit
Duration: 11:42 to 17:17 - 7 hours 35 minutes
Cause: Hurricane Alex (some scattered outages remained after this time)

July 21, 2004
Location: Buxton, Frisco, and Hatteras Substations, Ocracoke
Duration: 05:27 to 06:11 - 44 minutes
Cause: Lightning in Buxton 115/34.5kV Substation

June 11, 2004
Location: Frisco and Hatteras Substations, Ocracoke
Duration: 01:51 to 04:39 - 2 hr, 00 min (total, 5 interruption)
Cause: Lightning struck Buxton power Plant and Buxton transmission substation.

June 11, 2004
Location: Buxton 34.5 kV Substation
Duration: 01:51 to 04:36 - 1 hr, 36 min (total, 5 interruption)
Cause: Lightning struck Buxton power Plant and Buxton transmission substation.

May 22, 2004
Location: Buxton, Frisco & Hatteras Substations, Ocracoke
Duration: 21:08 to 21:46 - 38 min
Cause: Equipment malfunction. Voltage regulator control at Buxton caused 34.5 kV line to trip

May 4, 2004
Location: Avon Substation
Duration: 06:37 to 07:47 - 1 hr, 10 min
Cause: Buxton generating plant tripped line off during maintenance of transmission line.

March 17, 2004
Location: Waves Substation
Duration: 14:32 to 15:21 - 49 min
Cause: Switching problems during planned outage to maintain 115 kV switches at Oregon Inlet

March 17, 2004
Location: Avon Substation
Duration: 14:32 to 15:13 - 41 min
Cause: Switching problems during planned outage to maintain 115 kV switches at Oregon Inlet

March 13, 2004
Location: Avon Substation
Duration: 04:04 to 05:48 - 1 hr, 44 min
Cause: Perform maintenance on 115 kV switches

March 12, 2004
Location: Waves Substation
Duration: 04:02 to 05:47 - 1 hr, 45 min
Cause: Planned outage to repair 115 kV switch

March 8, 2004
Location: Waves Substation
Duration: 14:01 to15:20 - 1 hr, 19 min
Cause: Planned outage to repair 115 kV Switch at Waves Substation